Pressure Spring Type Overhead Line Fault Indicator

Quick Details Model Number: CBDL-JDX Brand Name: Chaobo Joint Type: Pressure Spring Type Application: Overhead 6-35KV High Voltage Cable IP Code: IP65 Place of Origin: Zhejiang, China (Mainland) Lead time for sample: Within 5 days ■ Function and Benefit ◆Indicate the fault line and fault point...

Products Specifications:

Quick Details

Model Number: CBDL-JDX 
Brand Name: Chaobo  
Joint Type: Pressure Spring Type  
Application: Overhead 6-35KV High Voltage Cable
IP Code: IP65  
Place of Origin: Zhejiang, China (Mainland)
Lead time for sample: Within 5 days

 

 Function and Benefit
◆Indicate the fault line and fault point quickly, lessen the blackout area;
◆Shorten troubleshooting time,improving electricity and power supply reliability;
◆Accurately indicate the instant fault, which is conducive to rule out the power supply problems;
◆Providing technical means for find the hidden permanent fault point;
◆Shorten the search time to find the fault point, reduce the labor intensity of line patrol person;
◆Defining the responsibility of the fault area and responsible people;
◆Avoiding traditional multiple switch out,switch on,line patrol to the effects of power equipment.
 

 Technical Parameters
◆Applicable voltage grade: U≥6-35KV
◆Applicable wire current: I≤1200A
◆Applicable wire diameter: 16mm sq≤D≤240mm sq
◆Action response time: 0.06s≤t≤3s
◆Reset time: 6,12,24,48H (Selectable, Default 24H)
◆Ambient temperature: -35 ℃ ≤T≤+70 ℃  
◆Operation times: ≥5000Times
◆Static power loss: ≤10μW
◆Protection class: IP65


 Action principle
Short circuit detection principle: According to the phenomenon of short circuit,the current break when  short circuit happen, the action on the basis of the protection movement power outages.
Used to judge the short circuit fault indicator diagram
图片1.png  
As line 2# B phase 2,5,8 indicator and line 2# C phase 3,6,9 indicator turn red, but the 11,12 indicator still show white, that judged the point D happen short circuit
Used to judge the grounding fault indicator diagram:
图片2.png  
As line 2# C phase 3,6,9 indicator turn red,but the 12 indicator still show white, that judged the point D happen grounding fault.

 